The BIG changes to CSA Z462 and arc flash PPE [webinar]

Feb 24, 2021

 

You can watch the full on-demand version of the webinar, which includes a Q&A section.
 
Webinar link: https://www2.levitt-safety.com/ArcFlashChangesGated
 
The CSA Z462 Technical Committee released the latest edition of CSA Z462 Workplace Electrical Safety Standards in January 2021.
 
You can imagine our excitement when Jim Pollard (yes that Jim Pollard) agreed to host our webinar on the major changes.
 
Jim is an award-winning electrical safety champion and voting member on the CSA Z462 Technical Committee.
 
Jim is also the Representative for Oberon Company in Canada. Oberon is a leading provider of arc flash personal protective equipment.
 
So who better than Jim to walk us through the major changes to the standard?
 
The BIG changes to CSA Z462 and arc flash PPE:
 
There were minor and major changes added to the 2021 edition of the standard including:
 
  • Revisions to footwear and outer layer requirements
  • Guidance on PPE requirements above 140 cal/cm2
  • New arc flash PPE category 5 (75 cal/cm2 minimum)
  • New arc flash PPE selection method (Annex V)
 
In the webinar, we focused mainly on the changes to arc flash PPE category 5.
 
This is the most significant change to the standard since 2004 when arc flash PPE categories were first introduced.
 
New arc flash PPE categories
 
 
What need does arc flash PPE category 5 address?
 
The point of the new category 5 is to address a gap in protection for work tasks involving electrical switchgear, which usually operates at 600 volts in Canada.
 
When someone calculates arc flash thermal incident energy, they use the engineering formulas found in the IEEE 1584 Guide for Performing Arc-Flash Hazard Calculations.
 
When the new formula is applied to 600-volt switchgear the calculated incident energy has significantly increased.
 
Since the basic principle of arc flash PPE selection is the protection must match or exceed the hazard, it meant the CSA Z462 Standard required a higher category to ensure workers were adequately protected.
 
The new category 5 has a minimum protection level that exceeds the worst-case scenario of 600-volt switchgear when using the CSA Z462 arc flash PPE category method.
 
New arc flash PPE selection method (Annex V)
 
The new edition of the Standard introduced a second method for arc flash PPE selection. Along with Table 6a which has been in previous editions, there is now Table V.1. This table is easier to use for electrical workers because it doesn’t require engineering knowledge or technical documents.
 
Jim outlined the differences between the two tables using this chart:
 
 
Using the new selection method option, the worker needs to identify the transformer size, fuse size or circuit breaker settings. With that information, they can easily select the appropriate category of arc flash PPE.
 
Quit sharing PPE:
 
Arc flash PPE, specifically suits and hoods, have been the most commonly shared items between workers.
 
The outbreak of COVID-19 provided obvious reasons for why workplaces must abandon this practice.
 
Arc flash PPE is made of porous and non-porous surfaces as well as multiple layers of fabric. This makes it difficult to clean and disinfect between uses.
 
Employers have two options now:
 
  1. Remove the shared PPE from service for effective cleaning between uses, or
  2. Purchase individually assigned equipment.
 
Upgrading your category 4 suits to category 5 suits:
 
Based on his experience, Jim said about 80% of the suits in workplaces right now are 40 cal/cm2 suits.
 
Chances are you will need to upgrade your category 4 arc flash PPE to category 5 because of this change to the CSA Standard.
 
This may seem obvious but it’s worth repeating that if your workplace has 40 cal/cm2 suit and your hazard is now requiring category 5 protection, you aren’t sufficiently protected.
 
If you’re exposed to 73 cam/cm2 thermal incident energy, which is possible with 600-volt switchgear (based on Table 6a parameters), you are likely to receive significant skin burns.
 

Source: https://www.levitt-safety.com/blog/big-changes-to-csa-z462/

SERVICE TECHNICIAN - VEHICLE FIRE SUPPRESSION TRAINEE

Levitt-Safety is currently recruiting a Vehicle Fire Suppression Technician trainee to train in the repair and maintenance of Vehicle Fire Suppression Systems, and other fire protection services. 

SERVICE TECHNICIAN - FIRE PROTECTION SERVICES / TECHNICIEN DE SERVICE

We are actively recruiting an experienced Services Technician to provide Fire & Life Safety Service and maintenance for Vehicle Fire Suppression, Fire Extinguishers, Instrumentation, and SCBA’s. 

SERVICE TECHNICIAN - FIRE PROTECTION SERVICES / TECHNICIEN DE SERVICE

We are actively recruiting an experienced Services Technician to provide Fire & Life Safety Service and maintenance for Vehicle Fire Suppression, Fire Extinguishers, Instrumentation, and SCBA’s. 

SERVICE COORDINATOR

As the service coordinator you will support the Oakville Service department by managing the day to day operations of the Service Department by scheduling service calls, coordinating the activities of our team of technicians, and for providing an exceptional customer service experience to both internal and external clients. 

SERVICE COORDINATOR

Reporting to the Service Administration Supervisor and working within a team environment, you will support the day-to-day operations of the Calgary Service Department by scheduling service calls, coordinating the activities of our team of technicians, and for providing an exceptional customer service experience to both internal and external clients. 

SERVICE ADMINISTRATIVE COORDINATOR

Levitt-Safety is actively seeking a Service Coordinator in our Port Coquitlam location to schedule mobile service technicians.

SERVICE ADMIN COORDINATOR - CONTRACT ROLE

Reporting to the Fort McMurray Service Admin Supervisor and working within a team environment, this position will support the day to day operations of the Fort McMurray Service Department by scheduling service calls, and to communicate with customers to determine and fulfill their service requirements. 

MOBILE SERVICE TECHNICIAN - FIRE & LIFE EQUIPMENT

Levitt-Safety is currently recruiting a Mobile Service Technician to provide the highest level of quality service to our customers in the repair and maintenance of Fire and Life Safety Equipment and other fire protection services.

MOBILE SERVICE TECHNICIAN - FIRE & LIFE EQUIPMENT

Levitt-Safety is currently recruiting a Mobile Fire Services Technician to provide the highest level of quality service to our customers in the repair and maintenance of Fire Extinguishers, Fire and Life Safety Equipment and other fire protection services. 

MOBILE SERVICE TECH – VEHICLE FIRE SUPPRESSION

Levitt-Safety is currently recruiting VFSS Technicians in Fort McMurray to provide the highest level of quality mobile service to our customers in the repair and maintenance of Vehicle Fire Suppression Systems and other fire and life protection services.