Home > Suppliers Companies > TES Inc. > Products > New Electrical Equipment > 750 KVA Mine Power Center
TES Inc.

750 KVA Mine Power Center

Ratings:
• Primary Voltage - 4160
• Secondary Voltage - 600
• Rated KVA - 750
• Frequency (Hz) -  60
• Number of Phases - 3
750 KVA Mine Power Center
Cutler Hammer 600V Distribution Panel with:
• 1- 800A main breaker with shunt trip up to 6- 400- 100A molded frame breaker with shunt trip
• Digital temperature display with relay
• Digital voltage/ current meters
 
Each breaker is protected by a Ground Fault & Ground Check Monitor (Startco SE-325 & SE- 105)