RG-Frame Breaker

Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems.

Introducing the Series G R-Frame 310+ breaker, featuring zone selective interlocking (ZSI), cause of trip, ground fault alarm (no trip) and Arcflash Reduction Maintenance System. The breaker is NEMA, UL, CSA and IEC listed with electronic trip unit.

800 - 2500 Amperes

Benefits of the R-Frame 310+ breaker:

• No DIP switches or rating plugs needed. The 310+ has adjustable trip settings integral to the electronic trip unit
• Remote Arcflash Reduction Maintenance System is an available feature. This feature increases worker safety by providing an accelerated instantaneous trip to reduce arc flash potential
• Ground fault alarm, no trip, is an option. In addition to offering ground fault and high load alarms, the 310+ allows for ground fault alarm, no trip. This is essential for critical applications that must stay online when a ground fault is present
• ZSI is an available feature. This feature enables the breaker to communicate with the immediate upstream or downstream ZSI-enabled breakers to clear faults in the shortest amount of time using the breaker closest to the fault o • All R-Frame circuit breakers are suitable for reverse-feed use

 

A full range of world-class accessories:

• Uses the same internal accessories as the standard R-Frame, from auxiliary switches to undervoltage relays
• Choose from a range of external accessories, including handle lock-offs, flex shafts, plug-in adapters and drawout cassettes
• In addition to integrated cause of trip, the RG 310+ built-in test port allows compatibility with Eaton's ammeter/cause of trip display, panelmount ammeter/cause of trip display, and cause of trip LED module

 

Trip unit features:

• No rating plug required
• Available with LS, LSI, LSG, LSIG and Arcflash Reduction Maintenance System via ALSI, ALSIG
• Trip units are factory installed and are available in these ranges:
   
     • 800-1600A
     • 1000-2000A
     • 1600-2500A

• Time current curves referenced in document TC01210019E
• Adjustable long-time delay
• Adjustable short-time delay
• Adjustable instantaneous
• Status indicator and no trip test indicator LEDs
• Push-to-trip button
• Integral cause of trip
• Optional devices that interface with the test port
     

     • Test kit
     • Ammeter/cause of trip display (DIGIVIEW)
     • Panelmount ammeter/cause of trip display (DIGIVIEWR06)
     • Cause of trip LED module (TRIP-LED)