Home > Suppliers Companies > Schneider Electric > Products > Starters > GV2 Miniature circuit breaker 0.63-1A
Schneider Electric

GV2 Miniature circuit breaker 0.63-1A

Series TeSys
Product name TeSys GV2
Device short name GV2P
Application area Engine
Release technology Thermomagnetic
GV2 Miniature circuit breaker 0.63-1A
Main Characteristics
 
Series TeSys
Product name TeSys GV2
Device short name GV2P
Application area Engine
Release technology Thermomagnetic
 
Additional Characteristics
 
Pole description 3P
Network type Alternating current
Utilization category AC-3 conforming to IEC 60947-4-1, Category A conforming to IEC 60947-2
Network frequency 50/60 Hz conforming to IEC 60947-4-1
installation method 35mm symmetrical DIN rail: fixed
Panel: screwed on (with 2 x M4 screws)
working position Any position
Engine power, kW 0.25 kW at 400/415 V AC 50/60 Hz, 0.55 kW at 690 V AC 50/60 Hz
Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 440 V AC 50 / 60 Hz conforming to IEC 60947-2, 100 kA Icu at 500, V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity (short-circuit) 100% at 690 V AC 50/60 Hz conforming to IEC 60947-2, 100% at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100% at 230/240 V AC 50/60 Hz conforming to IEC 60947 -2, 100% at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100% at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Control type Rotary handle
[In] rated current 1 A
thermal protection adjustment range 0.63 ... 1 A
Magnetic release current 13 A
[Ue] rated operating voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 1 A conforming to IEC 60947-4-1
[Up] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Power dissipated by one pole 2.5W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 440 V
Maximum switching frequency 25 cycle / h
Standard Application Continuous conforming to IEC 60947-4-1
connections - terminals Screw terminal 2 cable (s) 1 ... 6 mm² solid, Screw terminal 2 cable (s) 1.5 ... 6 mm² Flexible without, cable end Screw terminal 2 cable (s) 1 ... 4 mm² Flexible with cable end
torque 1.7 N.m on screw terminal
Insulation compliance Yes conforming to IEC 60947-1
Phase loss sensitivity Yes conforming to IEC 60947-4-1
Height 89 mm
Width 45 mm
Depth 97 mm