                                GV2 Miniature circuit breaker 0.16-0.25A
	Series TeSys
	Product name TeSys GV2
	Device short name GV2P
	Application area Engine
	Release technology Thermomagnetic
                        
	Main Characteristics
	Series TeSys
	Product name TeSys GV2
	Device short name GV2P
	Application area Engine
	Release technology Thermomagnetic
	Additional Characteristics
	Pole description 3P
	Network type Alternating current
	Utilization category AC-3 conforming to IEC 60947-4-1, Category A conforming to IEC 60947-2
	Network frequency 50/60 Hz conforming to IEC 60947-4-1
	installation method 35mm symmetrical DIN rail: fixed, Panel: screwed on (with 2 x M4 screws)
	working position Any position
	Engine power, kW 0.06 kW at 400/415 V AC 50/60 Hz
	Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 440 V AC 50 / 60 Hz conforming to IEC 60947-2, 100 kA Icu at 500, V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
	[Icu] rated ultimate short-circuit breaking capacity (short-circuit) 100% at 690 V AC 50/60 Hz conforming to IEC 60947-2, 100% at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100% at 230/240 V AC 50/60 Hz conforming to IEC 60947 -2, 100% at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100% at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
	Control type Rotary handle
	[In] rated current 0.25 A
	thermal protection adjustment range 0.16 ... 0.25 A
	Magnetic release current 2.4 A
	[Ue] rated operating voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
	[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
	[Ith] conventional free air thermal current 0.25 A conforming to IEC 60947-4-1
	[Up] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
	Power dissipated by one pole 2.5W
	Mechanical durability 100000 cycles
	Electrical durability 100000 cycles for AC-3 at 440 V
	Maximum switching frequency 25 cycle / h
	Standard Application Continuous conforming to IEC 60947-4-1
	connections - terminals Screw terminal 2 cable (s) 1 ... 6 mm² solid, Screw terminal 2 cable (s) 1.5 ... 6 mm² Flexible without, cable end Screw terminal 2 cable (s) 1 ... 4 mm² Flexible with cable end
	torque 1.7 N.m on screw terminal
	Insulation compliance Yes conforming to IEC 60947-1
	Phase loss sensitivity Yes conforming to IEC 60947-4-1
	Height 89 mm
	Width 45 mm